Abstract
Impedance-based analysis plays important role in assessing the stability and dynamics of grid-connected inverters and related systems. Measuring the inverter impedance is, however, not straightforward due to the load effect caused by the power grid. The power grid interacts with the inverter and produces additional (mirrored) frequency harmonics thus distorting the impedance measurements when applying conventional measurement techniques. This paper proposes an active-power filtering method to minimize the undesired load effect caused by the power grid in the measured impedance. Applying the method, the inverter output impedance can be reliably measured under non-ideal grid conditions.
Original language | English |
---|---|
Title of host publication | 2019 4th IEEE Workshop on the Electronic Grid (eGRID) |
Publisher | IEEE |
Number of pages | 6 |
ISBN (Electronic) | 978-1-7281-5704-7 |
ISBN (Print) | 978-1-7281-5705-4 |
DOIs | |
Publication status | Published - 2019 |
Publication type | A4 Article in conference proceedings |
Event | IEEE Workshop on the Electronic Grid - Duration: 1 Jan 1900 → … |
Conference
Conference | IEEE Workshop on the Electronic Grid |
---|---|
Period | 1/01/00 → … |
Publication forum classification
- Publication forum level 1