Examples of Electromagnetic Field Sources in an Indoor Distribution Substation

Rauno Pääkkönen, Marko Lundström, Jari Mustaparta, Leena Korpinen

    Research output: Chapter in Book/Report/Conference proceedingConference contributionScientificpeer-review

    Abstract

    The paper presents example measurements of electromagnetic fields in an indoor distribution substation. We measured at different places: At Place A (near the fuse panel), using (1) frequency bandwidth (FB) 40kHz-100kHz, fields varied 0.011-0.039 μT and using (2) FB 5Hz-100kHz, fields varied 67-74 μT; at Place B (the surface of the collector meter), the fields varied from 0.022 to 0.083 μT (40kHz-100kHz); at Place C (near the antenna of the collector meter), the maximum radio frequency field was 1.0 W/m2, and at Place D (the surface of the antenna), it was 1.8 W/m2. The measured values were below ICNIRP guidelines.
    Original languageEnglish
    Title of host publicationProgress In Electromagnetics Research Symposium, July 6-9, 2015, Prague, Czech Republic
    PublisherElectromagnetics Academy
    Pages561 - 564
    Number of pages4
    ISBN (Electronic)978-1-934142-30-1
    Publication statusPublished - 6 Jul 2015
    Publication typeA4 Article in conference proceedings
    EventProgress in Electromagnetics Research Symposium -
    Duration: 1 Jan 1900 → …

    Publication series

    NameProgress in electromagnetics research symposium
    ISSN (Print)1559-9450

    Conference

    ConferenceProgress in Electromagnetics Research Symposium
    Period1/01/00 → …

    Publication forum classification

    • Publication forum level 1

    ASJC Scopus subject areas

    • Engineering(all)
    • Electrical and Electronic Engineering

    Fingerprint

    Dive into the research topics of 'Examples of Electromagnetic Field Sources in an Indoor Distribution Substation'. Together they form a unique fingerprint.

    Cite this