Abstract
This paper presents the investigation of extremely low frequency magnetic fields at electric facilities of a hospital. We conducted 21 measurements (at electric facilities and other areas, for example, in the lobby and in the corridor). The magnetic fields were from 0.2 µT to 62.0 µT. The highest value was measured near the main circuit-breaker of the distribution board. Based on the measurements, the magnetic fields can be more than 50 µT in the technical areas of a hospital, which can cause disturbances in some medical devices.
Original language | English |
---|---|
Title of host publication | 2016 Progress in Electromagnetic Research Symposium (PIERS) |
Pages | 1413-1415 |
Number of pages | 3 |
ISBN (Electronic) | 978-1-5090-6093-1 |
DOIs | |
Publication status | Published - 10 Nov 2016 |
Publication type | A4 Article in conference proceedings |
Event | Progress in Electromagnetics Research Symposium - Duration: 1 Jan 1900 → … |
Conference
Conference | Progress in Electromagnetics Research Symposium |
---|---|
Period | 1/01/00 → … |
Keywords
- Area measurement
- Buildings
- Electric variables measurement
- Electromagnetics
- Hospitals
- Magnetic circuits
- Magnetic devices
Publication forum classification
- Publication forum level 1