Skip to main navigation Skip to search Skip to main content

Flux distribution analysis in three-phase Si-Fe wound transformer cores

  • George Loizos*
  • , Themistoklis D. Kefalas
  • , Antonios G. Kladas
  • , Athanassios T. Souflaris
  • *Corresponding author for this work

Research output: Contribution to journalArticleScientificpeer-review

42 Citations (Scopus)

Abstract

This paper shows experimental results of longitudinal flux density and its harmonics at the limb, the yoke and the corner of a three-phase, Si-Fe, five-legged wound transformer core. Results show that the flux density is nonuniform in the cores and there is high level of third harmonic component. Moreover, the lower flux values in the outer cores have been assessed and the simultaneous time variation of the flux in both outer cores has been demonstrated by measurements while the peak magnetic flux density values have been compared to FEM analysis. These findings enable a better understanding of the magnetic behavior of five-legged wound transformer cores and their consideration is expected to achieve respective improvement of the design with respect to core losses and magnetostriction noise.

Original languageEnglish
Article number5393109
Pages (from-to)594-597
Number of pages4
JournalIEEE Transactions on Magnetics
Volume46
Issue number2
DOIs
Publication statusPublished - Feb 2010
Externally publishedYes
Publication typeA1 Journal article-refereed

Keywords

  • Magnetic cores
  • Magnetic field measurement
  • Magnetic losses
  • Power transformers

ASJC Scopus subject areas

  • Electronic, Optical and Magnetic Materials
  • Electrical and Electronic Engineering