Abstract
The grid-connection point of photovoltaic inverters may exhibit inductive characteristics (i.e., a weak grid) due to long transmission cables as well as multiple transformers. A large grid impedance can arouse impedance-based stability problems, sustained resonances and impose power-delivery limits. This paper discusses an impedance-compensated synchronous reference- frame-PLL-angle-correction method. The method presented in this paper compensates the PLL angle according to estimated or measured grid impedance in order to achieve improved performance in weak grids. Due to the lack of explicit small-signal impedance models around the aforementioned topic, this paper presents a complete small-signal transfer function model to analyze the impedance-based stability of the PLL-angle compensation method. The results are validated with real-time hardware-in-the-loop simulations and laboratory experiments.
| Original language | English |
|---|---|
| Pages (from-to) | 347-355 |
| Journal | IEEE Transactions on Energy Conversion |
| Volume | 35 |
| Issue number | 1 |
| Early online date | 2019 |
| DOIs | |
| Publication status | Published - 2020 |
| Publication type | A1 Journal article-refereed |
Publication forum classification
- Publication forum level 2