Performance analysis of Q-f droop anti-islanding protection in the presence of mixed types of DG

    Tutkimustuotos: KonferenssiartikkeliTieteellinenvertaisarvioitu

    1 Sitaatiot (Scopus)

    Abstrakti

    This paper analyses the performance of a Q-f droop
    based anti-islanding protection (AIP) scheme when the islanded
    circuit contains both inverter based DG and directly connected
    synchronous generator (SG) based DG. It is found that the
    performance of the AIP method is significantly degraded when
    SG is present in the island. This is because frequency cannot be
    directly manipulated by injecting reactive power when SG is
    present. However, feeding reactive power still indirectly affects
    frequency and the Q-f droop based AIP scheme thus still
    facilitates islanding detection. The simulation results aim to
    bring awareness to which extent the presence of SG degrades the
    performance of the Q-f droop based AIP.
    AlkuperäiskieliEnglanti
    Otsikko2015 IEEE Innovative Smart Grid Technologies - Asia (ISGT Asia)
    Sivumäärä6
    ISBN (elektroninen)978-1-5090-1237-4
    DOI - pysyväislinkit
    TilaJulkaistu - marrask. 2015
    OKM-julkaisutyyppiA4 Artikkeli konferenssijulkaisussa
    TapahtumaIEEE PES Innovative Smart Grid Technologies Asian Conference - , Yhdysvallat
    Kesto: 1 tammik. 2000 → …

    Julkaisusarja

    Nimi2015 IEEE Innovative Smart Grid Technologies - Asia (ISGT Asia)
    ISSN (elektroninen)2378-8542

    Conference

    ConferenceIEEE PES Innovative Smart Grid Technologies Asian Conference
    Maa/AlueYhdysvallat
    Ajanjakso1/01/00 → …

    Julkaisufoorumi-taso

    • Jufo-taso 1

    Sormenjälki

    Sukella tutkimusaiheisiin 'Performance analysis of Q-f droop anti-islanding protection in the presence of mixed types of DG'. Ne muodostavat yhdessä ainutlaatuisen sormenjäljen.

    Siteeraa tätä